Loading... Please wait...

Our Newsletter


S8910U 1000 HSI CONTROL MODULE - S8910U1000

  • S8910U 1000 HSI CONTROL MODULE - S8910U1000
  • S8910U 1000 HSI CONTROL MODULE - S8910U1000
Price:
$386.80
SKU:
446-003
Brand:
Weight:
1.00 LBS
Shipping:
Calculated at checkout
Quantity:
Bookmark and Share


Product Description

S8910U 1000 HSI CONTROL MODULE - S8910U1000

Universal Hot Surface Ignition Module is designed to provide easy field replacement of a wide range of hot surface ignition modules manufactured by Honeywell, Robertshaw and White-Rodgers. The S8910U Module provides operating control of a direct ignition system using a 120 Vac hot surface igniter.

Features

    Replaces many White-Rodgers, Robertshaw and Honeywell hot surface ignition models.
    For 120 Vac (up to 5.0A) surface igniter (Norton 201/271 or equivalent).
    For local (single rod) or remote (dual rod) rectification type flame sensing.
    Contains easy-to-use instructions plus the accessories required to adapt the existing hot surface ignition module.
    Provides one or three ignition trials (four-second or seven-second trials) per call for heat; prepurge of 32 seconds or less; up to 96 seconds between purge trial times.
    Temperature range is -40 to +175 F (-40 to +79 C).

Replaces Old Numbers:  

085267141246, 1001346, 21N34, 21N34-S8910U100, 50E47-150, 50E47-170, 50E47-50, 50E47843S1, 50F47-060, 780-784, 786710006500, 786710111235, H1001346, S890C1007, S890D1006, S890G1003, S890G1011, S890G1029, S890G1037, S890H1002, S890H1010, S890H1028, S89C1004, S89C1012, S89C1046, S89C1079, S89H1011, S89H1029, S89J1008, W609192, W619033

Specifications

    Description: Provide electronic control of direct hot surface ignition systems used on gas fired furnaces, boilers, and other heating appliances.
    Ignition System Type: Direct Hot Surface Ignition
    Ignition Sequence: The number of trials for ignition and trial time is determined by the selection tab. If a selection tab is not installed, the module will operate at four seconds trial time and one ignition trial.
    Typical Gas Control: VR8205, VR8305
    Type of Gas: Natural or LP
    Flame Sense: Single Rod or Two rods
    Ignition Source: Line Voltage (120 VAC) Hot Surface Element (Norton Model 201 or 270)
    Prepurge: 32 Seconds
    Ignition Trials To Lockout: 1 or 3
    Lockout Timing: 4 Sec. or 7 Sec
    Ignition Trial Time: 4 sec. or 7 sec.
    Maximum Valve Load @ 24 Vac (Amps): 2A
    Typical Ignition Hardware: Norton 201, Norton 271, Q354A
    Dimensions: 5 1/4 in. high x 4 1/16 in. wide x 1 15/16 in. long
    Electrical Ratings: 24 Vac
    Frequency: 60 Hz
    Max Ambient Temperature: -40 F to +175 F
    Between Trial Time: (2) 96 sec. – 3 trial mode only
    Flame Failure Response Time: 1.5 sec


Find Similar Products by Category


Write your own product review

Product Reviews

This product hasn't received any reviews yet. Be the first to review this product!